Fire batt and fire-rated board
For the openings that are too big for a tube of mastic.
- Every seal labelled and photographed
- BM TRADA / FIRAS-certificated contractors
- Written price before any work
A cable tray carrying forty cables, a 54mm copper pipe and a plastic waste, all coming through one ragged hole in a riser wall about 300 by 200mm. Mastic will not close that. The usual answer is a coated fire batt: a slab of dense mineral wool, 50 or 60mm thick, coated grey or white on both faces, cut to fit the opening tightly and then cut again around each service. Every joint and edge gets mastic from the same tested system, the plastic waste gets its own collar or wrap, and the copper pipe may need a wrap as well where the test calls for it.
Some tested details use one batt in the middle of the wall, others use two, one on each face. The manufacturer's data says which, for that wall and that set of services.
Bigger holes, such as an old opening left where a duct was taken out, are sometimes closed with fire-rated board fixed to the wall around the opening, with any remaining services sealed through it. Board is also used to box in a group of pipes where they pass through a floor.
Batts are soft. The classic fault is a new cable pushed through with a screwdriver and never sealed round. The work in Reading is carried out by our BM TRADA / FIRAS-certificated contractors, and each batt is labelled and photographed.

Send the postcode, the type of building and a photo of the gap with a tape measure in the shot. We reply with what it needs and a written price.